Gaseous Fire Suppression Systems

Apreco Limited Gas Fire Suppression Systems ImageDemand for Apreco fire suppression vents is increasing with the recognised need for over-pressure venting associated with high pressure Gas Fire Suppression Systems.

With inert gases and mixtures being supplied in high volumes to reduce oxygen concentration to suppress a fire, there is potential to cause structural damage if no means of pressure venting is provided. Buildings are most commonly designed to withstand internal pressures of between 250 to 500Pa, though this can vary depending on the type of construction.

Apreco FSV pressure relief vents are designed to prevent the risks of over pressurisation resulting from the use of gas fire suppression systems. The FSV range of pressure relief vents have been successfully tested to EN1363-1 criteria to provide a 2-hour fire resistance rating.

Specifically developed for this application, the range can be used alongside a wide range of gas fire suppression systems to prevent structural damage and risk to personnel.

The vents can provide up to 85% free venting area (FVA), thus reducing the space taken up by the units and the cost of installation.

Maximum room pressure is controlled by the vents opening to allow air to escape, then closing when discharge is complete. This maintains the dilution of the air, so preventing re-ignition.

The range of options include low loss external weather louvres, internal egg crate cover grilles.